Sensor for the measurement of chlorine dioxide. Membrane-covered, amperometric 2-electrode system. 

  • Measurand(s): chlorine dioxide
  • Calibration: at the controller, am Controller, via analytical chlorine-dioxide determination by DPD-1 method 
  • Interferences: Cl2 is being registered with factor 0,03 of ist measured value, O3 is also registered
  • pH range: 1 … 11
  • Pressure range: 0 …1 bar, no pressure surges and/or fluctuations
  • Temperature range: 0 … 45 0C (no ice crystals in measurement water)
  • Integrated automatic temperature compensation
  • Response time: T90 approx. 15 s
  • Flow rate: approx. 30 l/h, low flow-dependence
  • Shaft length: standard 175 mm, and up to 220 mm in length (mA-Version),
  • Connection: standard 4-pole plug; for mA-version 2-pole terminal, M12 male or Modbus RTU with M12 male
  • Material: PVC-U, semipermeable membrane
Datasheet
Request product

Product request

Request